The device is designed to control one fire extinguishing zone, control modules and generators of powder, aerosol  and gas fire extinguishing of one zone, organize sequential cascade control  of several devices  for the electric start of a fire extinguishing agent generator activated by a single signal.

 Basic technical data:

  • Number of message types  -  22;
  • Number of alarm loop operation algorithms - 4;
  • Output voltage of the main power source - (15 ± 0.1) V;
  • Current range in the alarm loop circuit, at which the standby mode is set, from 5 mA to 17 mA;
  • The current in the circuit of the alarm system, which is estimated as a short circuit, not less than 26 mA;
  • Operating time from the backup source:  in STANDBY mode, not less than 24 hours; in ALARM mode, not less than 3 hours;
  •  DC battery 12V 7Ah;
  •  Number of messages about the status of the device's power supply  –  4;
  •  The device's operating mode is round the clock and continuous.